NEC Article 220 — Dwelling Unit Load Calculator

220.12 General Lighting & Receptacles

Connected VA = Floor Area (ft²) × 3 VA/ft² Table 220.42 Demand Factors: First 3,000 VA → 100% 3,001–120,000 VA → 35%

220.52(A) Small Appliance Circuits

Minimum 2 circuits × 1,500 VA = 3,000 VA (100% demand — folded into Table 220.42) Each additional circuit: +1,500 VA

220.52(B) Laundry Circuit

1 circuit × 1,500 VA = 1,500 VA (100% demand — folded into Table 220.42)

220.53 Fixed Appliances

If 4 or more appliances (excluding dryer, range, A/C, heating): Demand = Sum of nameplate ratings × 75% If fewer than 4: Demand = Sum of nameplate ratings × 100%

220.55 / Table 220.55 Electric Range / Oven

1 range ≤ 12 kW (Column C): 8 kW demand For 1 range > 12 kW: 8 kW + 5% per kW above 12 kW Multiple units: use Table 220.55 Column C, then adjust for kW > 12 Note: Column C values (1–3 units, rated ≤ 12 kW) shown below. 1 unit → 8 kW demand 2 units → 11 kW demand 3 units → 14 kW demand

220.54 / Table 220.54 Electric Dryer

Demand = Greater of 5,000 W or nameplate VA (for 1 dryer, 100% demand)

220.60 Heating & Air Conditioning

Use the LARGER of heating or cooling — not both (non-coincident loads). Demand = max(Heating VA, Cooling VA)

Summary & Service Size

Load Category Connected VA Demand Factor Demand Load VA
Total Calculated Demand Load —
Total Demand (VA) —
Minimum Amps @ 240V —
Recommended Service Size —

Study aid only — verify against the adopted code edition / a licensed professional before use in real project/estimate documentation.
References: NEC 2023, Article 220 (Branch-Circuit, Feeder, and Service Load Calculations).