NEC Grounding & Bonding Conductor Sizing Calculator

NEC 2023

Grounding Electrode Conductor (GEC) Sizing

NEC 2023 — Section 250.66 & Table 250.66

Select a conductor size above to see the required GEC.

Equipment Grounding Conductor (EGC) Sizing

NEC 2023 — Section 250.122 & Table 250.122

Enter the OCPD rating above to see the required EGC.

250.122(B) — Increased Size: Where the circuit conductors are increased in size from the minimum required, the EGC shall be increased proportionately. This calculator gives the minimum size per Table 250.122.

Main Bonding Jumper (MBJ) & Supply-Side Bonding Jumper (SSBJ)

NEC 2023 — Sections 250.28, 250.102 & Table 250.66

Select a conductor size above to see the required bonding jumper size.

250.102(C)(1) — Multiple Conductors in Parallel: Where the service-entrance conductors are installed in parallel, the bonding jumper shall be sized based on the equivalent area of the largest phase conductor per phase (sum of parallel conductors of the same size and material), and the result looked up in Table 250.66.

12.5% Rule (250.102(C)(1) Exception): Where the service-entrance conductors exceed the maximum in Table 250.66, the bonding jumper is permitted to be sized at not less than 12.5% of the equivalent circular mil area of the largest phase conductor, selecting the next standard size from Table 250.66 or higher.

NEC 2023 Table 250.66 — GEC & Bonding Jumper Sizing

Section 250.66; also governs MBJ/SSBJ per 250.28 & 250.102

Largest Service-Entrance Conductor
(or Equivalent for Parallel)
GEC / Bonding Jumper Size
Copper (Cu) Aluminum / CCA (Al) Copper GEC Aluminum GEC
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 AWG or 3/0 AWG6 AWG4 AWG
2/0 AWG or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 thru 350 kcmilOver 250 thru 500 kcmil2 AWG1/0 AWG
Over 350 thru 600 kcmilOver 500 thru 900 kcmil1/0 AWG3/0 AWG
Over 600 thru 1100 kcmilOver 900 thru 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil

NEC 2023 Table 250.122 — EGC Sizing

Section 250.122 — based on OCPD rating ahead of circuit

OCPD Rating (A) Copper EGC Aluminum / CCA EGC
1514 AWG12 AWG
2012 AWG10 AWG
3010 AWG8 AWG
4010 AWG8 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
5002 AWG1/0 AWG
6001 AWG2/0 AWG
8001/0 AWG3/0 AWG
10002/0 AWG4/0 AWG
12003/0 AWG250 kcmil
16004/0 AWG350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil750 kcmil
5000700 kcmil1200 kcmil
6000800 kcmil1200 kcmil

Conductor Area Reference (kcmil)

Used for 12.5% rule calculations

SizeCircular Mils (CM)12.5% of CM
Study aid only — verify against the adopted code edition / a licensed professional before use in real project/estimate documentation. This calculator implements NEC 2023 Table 250.66 and Table 250.122 logic. Local amendments, parallel conductor configurations, and special conditions (e.g., 250.66(A)–(C) caps for certain electrode types) may alter the required size.